The Intesis MHI gateway was switched from Modbus TCP to native MQTT mode (2026-08-13), publishing retained per-signal JSON status to hvac/mhi/IU<nn>/status/<signal> and subscribing to commands at hvac/mhi/IU<nn>/cmd/<signal>Cmd. This adds an MQTT ingest + command path alongside the now-dormant Modbus driver, under a new mhi_mqtt device type. Backend: - lib/mqtt.js: subscribe hvac/mhi/+/status/+, parse JSON payloads, auto- register each unit as an unassigned mhi_mqtt zone_devices row and cache live status (power/mode/setpoint/room temp/fan/health). Add publishMhiCommand() for on/off/mode/setpoint/fan/vanes writes (QoS 1, retain off — a retained command would replay stale on gateway reconnect). Numeric mode/fan enums map index-for-index to the frontend label arrays. - routes/override.js: mhi-status/mhi-control branch on device_type — mhi_mqtt serves from the push-populated cache and publishes commands; mhi_modbus keeps its synchronous register path unchanged. - routes/devices.js: discover() note for mhi_mqtt (units self-register). - No DB migration: existing status columns cover it. Credentials: getCredentials() now prefers env-injected creds (MQTT_BROKER_HOST/USERNAME/PASSWORD) over the settings fetch — the broker hashes each dynsec client password show-once, so it can't be re-served from settings at runtime. Compose passes the new env through. Frontend: add mhi_mqtt to DeviceType/labels/implemented list, render MhiControlPanel and count it as an AC device type. Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com> |
||
|---|---|---|