standalone connection test script Register map derived and validated from two real Intesis MAPS signals exports (2-unit and 11-unit) taken from the physically installed gateway. The 11-unit export overturned an earlier assumption from the config screen's "Fixed" addressing label: register slots are dense in config/commission order, not fixed-per-IU with gaps — so a unit's register base must come from the imported map (or be entered manually), never computed from room number or SuperLink IU address. - drivers/mhi-profiles/intesis-mhi-modbus.js: register map + encodings for the confirmed gateway (TCP, port 502, slave 1, single-slave mode), documenting the corrected slot-vs-IU distinction - lib/mhi-xlsx-import.js: parses an Intesis MAPS signals export into a structured per-unit register map (0 unmatched rows against both real samples) — this becomes the authoritative Phase 2 source of truth, with the static profile only a pre-first-export fallback - scripts/test-modbus-connection.py: dependency-free Modbus TCP test (validated against a local loopback mock server) to resolve the one remaining open question — the address-base convention — directly from the Proxmox host, which already sits on the trusted admin VLAN - docs/: both real MAPS export samples, preserved as provenance Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>