There was no way to remove an mhi_gateways row either, alongside the
already-fixed device-delete gap — exposed by the same Modbus->MQTT
switchover. Adds DELETE /api/mhi-gateways/:id (manage_devices cap) and a
'Delete gateway' button. Devices referencing the gateway are NOT deleted
(mhi_gateway_id just goes NULL per the existing ON DELETE SET NULL FK) —
the confirm dialog says so and points at the separate device-delete flow
for retiring the stale mhi_modbus rows too.
Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
There was no way to remove a zone_devices mapping — a gap exposed by the
Modbus->MQTT switchover, which leaves the old mhi_modbus rows stale beside
the freshly auto-registered mhi_mqtt ones. Adds DELETE /api/devices/:id
(manage_devices cap, unlinks photo files then deletes; device_photos
cascade) and a 'Delete device' button in the expanded device row.
Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
The Intesis MHI gateway was switched from Modbus TCP to native MQTT mode
(2026-08-13), publishing retained per-signal JSON status to
hvac/mhi/IU<nn>/status/<signal> and subscribing to commands at
hvac/mhi/IU<nn>/cmd/<signal>Cmd. This adds an MQTT ingest + command path
alongside the now-dormant Modbus driver, under a new mhi_mqtt device type.
Backend:
- lib/mqtt.js: subscribe hvac/mhi/+/status/+, parse JSON payloads, auto-
register each unit as an unassigned mhi_mqtt zone_devices row and cache
live status (power/mode/setpoint/room temp/fan/health). Add
publishMhiCommand() for on/off/mode/setpoint/fan/vanes writes (QoS 1,
retain off — a retained command would replay stale on gateway reconnect).
Numeric mode/fan enums map index-for-index to the frontend label arrays.
- routes/override.js: mhi-status/mhi-control branch on device_type —
mhi_mqtt serves from the push-populated cache and publishes commands;
mhi_modbus keeps its synchronous register path unchanged.
- routes/devices.js: discover() note for mhi_mqtt (units self-register).
- No DB migration: existing status columns cover it.
Credentials: getCredentials() now prefers env-injected creds
(MQTT_BROKER_HOST/USERNAME/PASSWORD) over the settings fetch — the broker
hashes each dynsec client password show-once, so it can't be re-served from
settings at runtime. Compose passes the new env through.
Frontend: add mhi_mqtt to DeviceType/labels/implemented list, render
MhiControlPanel and count it as an AC device type.
Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
Adds actual room-temperature capture for TRVs over MQTT and a background
Modbus poller for AC mode/fan/lock/room-temp, so the dashboard tile can show
real setpoint-vs-actual readings, an AC status block, and up to 3 radiator
icons per zone instead of just the setpoint.
Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
Manual on/off/mode/setpoint/fan control for MHI indoor units via the
already-verified Intesis Modbus TCP gateway, deliberately NOT wired into
the NewBook-driven scheduler yet — that stays deferred. Modbus doesn't
depend on the MQTT broker (separate infra, still unbuilt), so this can be
deployed and tested standalone.
- mhi_gateways table (connection config: host/port/slave id/address base)
+ zone_devices columns for MHI devices (gateway id, unit index, IU hint,
and the per-device register map staged from a MAPS import — ground
truth, never re-derived from room/IU at runtime)
- drivers/mhi-modbus.js: discover/getStatus/setTarget over modbus-serial,
same interface as trv.js/homeassistant.js; per-gateway request queue
since Modbus TCP requires serialised requests; falls back to the
profile's stride formula (with a loud warning) only if a unit has never
been through an import
- routes/mhi-gateways.js: gateway CRUD, live test-connection, xlsx import
(stages the parsed result for review — never auto-creates devices),
per-unit 'assign to zone' as the explicit commit step
- routes/override.js: GET .../mhi-status, POST .../mhi-control (control cap)
- frontend: GatewaysPanel (add gateway, test connection, import + preview,
assign units) and MhiControlPanel (on/off, mode, setpoint, fan) wired
into Devices.tsx / ZoneDetailModal.tsx
Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
Ports the state machine, retry/backoff, and guest-override detection from
the retired homeassistant-newbook-heating-component, without depending on
Home Assistant. Backend (Fastify/pg) + frontend (React/Vite/TS) following
standard stack conventions; LXC 128 (127 was already taken by utilities).
MHI/Midea/Daikin/boiler drivers and the shared MQTT broker (LXC 104) are
later phases/infra, not included here.
Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>