Commit graph

4 commits

Author SHA1 Message Date
d10e4884b8 Add global occupied/vacant default templates with per-room overrides
Settings gains a 'Default Templates' section: arrival-prep/departure-prep offsets,
a default aircon template (on/off, mode, setpoint, fan speed x occupied/vacant), and
default TRV setpoints. Every room can individually override any of these fields via
per-field 'Override' toggles in its Schedule modal, falling back to the global
default when not overridden.

Backend:
- zones table: occupied_temp/vacant_temp/heating_offset_min/cooling_offset_min are
  now nullable (NULL = inherit default); existing values preserved as explicit
  per-room overrides, so no room's behaviour changes on deploy. 8 new nullable
  ac_occupied_*/ac_vacant_* override columns.
- New 'hvac_defaults' config key (generic config store) holds the global template.
- scheduler.js: resolves each field as zone-override ?? global-default, and now
  also drives AC state automatically on occupancy transitions (previously AC was
  100% manual) via the same command path the manual control panel uses.
- lib/ac-control.js: factored the mhi_mqtt/mhi_modbus command logic out of
  routes/override.js so the scheduler and the manual control route share one path.
- zones.js PATCH: explicit-null-clears-override semantics for the 12 overridable
  fields (distinct from omitting the key, which leaves the value unchanged).

Frontend:
- Settings.tsx: new Default Templates section matching the requested layout.
- ZoneDetailModal.tsx: per-field Override checkboxes for offsets, AC
  occupied/vacant template, and TRV occupied/vacant setpoints.

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
2026-08-25 09:48:28 +00:00
c873e4a270 hvac: native MQTT driver for MHI aircon (replaces Modbus for control/status)
The Intesis MHI gateway was switched from Modbus TCP to native MQTT mode
(2026-08-13), publishing retained per-signal JSON status to
hvac/mhi/IU<nn>/status/<signal> and subscribing to commands at
hvac/mhi/IU<nn>/cmd/<signal>Cmd. This adds an MQTT ingest + command path
alongside the now-dormant Modbus driver, under a new mhi_mqtt device type.

Backend:
- lib/mqtt.js: subscribe hvac/mhi/+/status/+, parse JSON payloads, auto-
  register each unit as an unassigned mhi_mqtt zone_devices row and cache
  live status (power/mode/setpoint/room temp/fan/health). Add
  publishMhiCommand() for on/off/mode/setpoint/fan/vanes writes (QoS 1,
  retain off — a retained command would replay stale on gateway reconnect).
  Numeric mode/fan enums map index-for-index to the frontend label arrays.
- routes/override.js: mhi-status/mhi-control branch on device_type —
  mhi_mqtt serves from the push-populated cache and publishes commands;
  mhi_modbus keeps its synchronous register path unchanged.
- routes/devices.js: discover() note for mhi_mqtt (units self-register).
- No DB migration: existing status columns cover it.

Credentials: getCredentials() now prefers env-injected creds
(MQTT_BROKER_HOST/USERNAME/PASSWORD) over the settings fetch — the broker
hashes each dynsec client password show-once, so it can't be re-served from
settings at runtime. Compose passes the new env through.

Frontend: add mhi_mqtt to DeviceType/labels/implemented list, render
MhiControlPanel and count it as an AC device type.

Co-Authored-By: Claude Opus 4.8 (1M context) <noreply@anthropic.com>
2026-08-13 13:31:01 +00:00
e5c40bbb8c Add MHI aircon manual control (Phase 2, Modbus only)
Manual on/off/mode/setpoint/fan control for MHI indoor units via the
already-verified Intesis Modbus TCP gateway, deliberately NOT wired into
the NewBook-driven scheduler yet — that stays deferred. Modbus doesn't
depend on the MQTT broker (separate infra, still unbuilt), so this can be
deployed and tested standalone.

- mhi_gateways table (connection config: host/port/slave id/address base)
  + zone_devices columns for MHI devices (gateway id, unit index, IU hint,
  and the per-device register map staged from a MAPS import — ground
  truth, never re-derived from room/IU at runtime)
- drivers/mhi-modbus.js: discover/getStatus/setTarget over modbus-serial,
  same interface as trv.js/homeassistant.js; per-gateway request queue
  since Modbus TCP requires serialised requests; falls back to the
  profile's stride formula (with a loud warning) only if a unit has never
  been through an import
- routes/mhi-gateways.js: gateway CRUD, live test-connection, xlsx import
  (stages the parsed result for review — never auto-creates devices),
  per-unit 'assign to zone' as the explicit commit step
- routes/override.js: GET .../mhi-status, POST .../mhi-control (control cap)
- frontend: GatewaysPanel (add gateway, test connection, import + preview,
  assign units) and MhiControlPanel (on/off, mode, setpoint, fan) wired
  into Devices.tsx / ZoneDetailModal.tsx

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
2026-07-27 14:43:38 +00:00
276c04f8c6 Scaffold Phase 1 hvac app — NewBook-driven room TRV heating scheduler
Ports the state machine, retry/backoff, and guest-override detection from
the retired homeassistant-newbook-heating-component, without depending on
Home Assistant. Backend (Fastify/pg) + frontend (React/Vite/TS) following
standard stack conventions; LXC 128 (127 was already taken by utilities).

MHI/Midea/Daikin/boiler drivers and the shared MQTT broker (LXC 104) are
later phases/infra, not included here.

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
2026-07-26 18:00:42 +00:00