Fix: scheduler never automated Daikin AC — missing from AC_DEVICE_TYPES

routes/override.js and ac-control.js's commandAcDevice() got a daikin branch when the
driver was built, but scheduler.js's own separate AC_DEVICE_TYPES filter (used for
automatic occupied/vacant scheduling at room state transitions) was never updated —
so every scheduler tick for a zone with only a daikin device logged "No devices to
command" and silently skipped it. Manual control worked fine (different code path),
which is why it wasn't caught until a real unit got stuck on after a manual test.

Note: this does NOT retroactively fix a unit already stuck from a missed transition —
the scheduler only applies at state transitions, not continuously, so a currently-on
unit needs a manual off (or the next real transition) to actually turn off.